DILO Home > Documentation > Competition Comparison

Portable "Dolly" Mounted SF6 Recovery System Comparison

Feature

DILO

MINI Plus II

Brand A

Brand B

Brand C

Liquefaction (process)

Yes, direct pressure

Yes, cooling assisted

Yes, cooling assisted

No, insignificant pressure

Contains oil

No

No

Yes

No

Compressor used during re-fill

Yes

No

No

Yes

Maximum delivery rates (LB/min)

1

.5

.4

.5

Displacement (CFH)

75 CFH

35 CFH

30 CFH

30 CFH

Maximum compressor output (psig)

725 psig

475 psig

460 psig

375 psig

Maximum vacuum while suctioning SF6 (mmHg)1

35 mmHg

1,300 mmHg

400 mmHg

1100 mmHg

Compression ratio

1000:1

20:1

60:1

20:1

Maximum capacity
(on-board)

230 lbs.

150 lbs.

50 lbs.

20 lbs.

Weight of unit (complete)2

240 lbs.

420 lbs.

185 lbs.

135 lbs.

Vacuum pump speed (CFM)

10 CFM

11 CFM

3 CFM

6 CFM

Vacuum pump capacity (micron)

10 micron

1000 micron

500 micron

100 micros

Self sealing fittings (type)

Yes, DILO

No

Yes, Aeroquip?

No

Cylinder consolidation

Yes

No

Yes, limited

No

Storage method

SF6 cylinder

ASME tank*

SF6 cylinder

Refrigerant tank, non-approved*

Valves

3

10

6

6

Maximum percentage recovered3

99.34%

75.56%

92.48%

79.32%

 

These values were taken from sales literature from each of the respective manufacturers.

1 Using the manufacturers’ published compression ratios, the following formula was used to obtain correct final pressures: Convert maximum compressor output pressure to mmHg.
This value is then divided into the compression ratio.

( (PSIG +14.5) : 14.5) x 760 = mmHg (absolute)


2 This does not include the weight of cylinders, since various sizes/weights can be used.


* Refrigeration vessels, and ASME tanks are not DOT approved for SF6.
Transportation of these vessels with internal pressures greater than 41 psig, is in violation of CFR 173.


3 See "Determining How Much Gas Has Been Recovered" page for formulas used to derive percentages.