DILO Home > Analyzers > Decomposition Detection Device > 3-032-R050
SF6 Decomposition Detection Device 3-032-R050
Description
The DILO 3-032-R050 decomposition detector is a stand-alone device designed to quickly and accurately measure the amount of sulfur dioxide (SO2), and thionyl fluoride (SOF2) in faulted SF6.
Because the unit contains an automatic flow and pressure control module, the user does not need to be concerned with setting the correct flow rate, or compensating for variations in equipment pressure. In fact, the device can handle up to 500 PSIG inlet pressure – making it a perfect fit for testing directly from cylinders, without the need for a (potentially contaminating) pressure regulator. All readings are displayed real-time on the touch-screen display, in parts per million by volume (PPMv).
The 3-032-R050 decomposition detector has been designed, from the ground up, to be used on arced SF6. Unlike conventional decomposition testers, which require expensive spectrometers or disposable detector tubes, this unit uses an electro-chemical sensor. While the sensor must be replaced (by the user) every 12 months, its accuracy and sensitivity do not degrade due to use. Calibration is not required.
The universally accepted CIGRE B3.02.01 standard for re-usable SF6 is currently 12 PPMv for SO2/SOF2 – which falls well within the 0-100PPMv range of the 3-032-R050
Technical Specifications
- Connections DILO self-sealing quick disconnects
- Input pressure 8 PSIG to 500 PSIG
- Flow rate 20 liters per hour or 3.2 oz. per hour or approximately 0.3 oz per test
- Operations Purge valve to vent contents of hose
- Display Touch-screen LCD 240 x 128 pixels
- Power supply Lithium Ion rechargeable batteries (8hour);
100-265 VAC with battery status indicator
- Operating temp 32°F to 122°F
- Dimesions 11"L x 5.5"W x 11.75"H, 13 lbs
- Measuring range 0-100 PPMv SO2 SOF2
- Resolution 1 PPMv
- Response time < 15 seconds
- Moisture limit Up to 90% RH, non-condensating
- Life span 6 month sealed in foil bag; 12 month from installation in analyzer
- Max. Zero shift 0.1 PPMv
- Drift < 2% signal degradation per month (linear)
- Flow rate 20 liters per hour or 6.4 oz of SF6 per hour or 0.3 oz per test
- Calibration None required
Characteristics
- Compact, lightweight
- Low maintenance
- Cost-effective
- Highly sensitive
- Touch-screen interface
- Fast test results, typically <15 seconds
- AC or battery power (8 hours)